Menu

Gensets

150 kVA Generator

  • 150 kVA Prime Power Rating
  • Diesel Engine
  • Trailer Mounted

POWER

Engine Type

Volvo TAD/720GE

Generator Type

Taiyo

Standby Power Rating

Single Phase 120V

396 amps (L1-N, L3-N at load)

Single Phase 240V

396 amps

Three Phase 208V

433 amps

Three Phase 480V

198 amps

Prime Power Rating

Single Phase 120V

363 amps (L1-N, L3-N at load)

Single Phase 240V

363 amps

Three Phase 208V

394 amps

Three Phase 480V

180 amps

GENERATOR SPECIFICATIONS

Voltage - Three Phase

208, 220, 240, 416, 440, 480V - Switchable

Voltage - Single Phase

120, 127, 139, 240, 254, 277V - Switchable

Excitation

Brushless with AVR

Voltage Regulation

0.5% (No Load to Full Load)

Insulation

Class F

Power Factor

0.8

Frequency

60 hertz

Generator RPM

1,800 rpm

Standby Output

132kW/165kVA (Three Phase), 95kW/95kVA (Single Phase)

Prime Output

120kW/150kVA (Three Phase), 87kW/387kVA (Single Phase)

Number of Poles

4

Armature Connection

Star with Neutral/Zig Zag

ENGINE SPECIFICATIONS

Engine Design

4-Cycle,6 Cyl., Water-Cooled, Direct Injection Turbocharged

Displacement

436 cu in

Bore x Stroke

4.3 x 5.1 in

Horsepower

190.4hp @ rated speed

Fuel Consumption

8.7 gph @ Full Load

 

6.5 gph @ 75% Load

 

4.7 gph @ 50% Load

Coolant/Oil Capacity

6.7/5.4 gal

Battery/Starting System

12V DC/Electric

WEIGHTS AND DIMENSIONS

Overall L x W x H

119 x 46 x 58 in

Approx. Net Dry Weight

5,137lbs

Sound Level ¬‚¬Å“ Full Load

72 dB(A) @ 23 ft

Skid Fuel Tank Capacity

66 gal

Trailer Fuel Tank Capacity

150 gal

 

 

Insert form here.